Technical specifications:
• Graphic display 128 x 64 bits;
• Front keyboard for navigation and configuration;
• Phase Universal Network measurements with 2 or 3 measuring elements, three or four-wire (delta or star connection);
• Current Measurements (L1, L2, L3 and N) with internal CT to 5A;
• Signal Limit 10% to 120%;
• Voltage Measurement (L1, L2, L3);
• L voltage – N (63V, 127V, 220V, 254V);
• Voltage L – L (110V, 220V, 380V, 440V);
• Signal Limit 10% to 120%;
• Class Accuracy Measures 0.25% for all types of outputs;
• Total of 4 optional analog outputs 4 to 20 mA (maximum load of 750 Ω) or 0-10 Vdc or 0-5VDC;
• All outputs must share the same common point;
• Total 4 optional outputs open collector;
• The 4 outputs can be configured as any variable alarms;
• The 4 outputs can be configured as 6545 pulses to 36000 / h proportional selected variables. The pulse width can be set from 50 to 500 ms per regardless output;
• Output require external power (maximum 60Vcc is typical of 24 Vdc) and are able to supply 20mA per output;
• Non-volatile data memory for mass storage;
• The data stored shall contain: Year, Month, Day, Hours, Minutes and, in addition to the previously set measurement variables;
• It can be configured up to 20 variables and time intervals of 1 second to 60 minutes;
• Nominal Frequency 47Hz to 63Hz;
• Operating temperature from 0 ° to 60 ° C;
• Insulation:
• Between power and the rest: 2.5KV / min – 60Hz;
• Between RS485 and Digital Outputs: 0.5 KV / min;
• Universal Source: – (85-240) AC; – (90-300) Vcc; – Lower consumption 10 VA
• RS-485:
• Modbus-RTU protocol for communication with supervisory and configuration software;
• Baud-rates: 9600 bps, 19200 bps, 57600 bps, 115,200 bps;
• Profibus-DP protocol for communication with master (optional to be developed in version 2);
• Protection: IP20 – panel mounting;
• Dimensions (W x H x D) 96 x 96 x 155mm.